NFA2X (XLPE İZOLELİ) HD 626

NFA2X (XLPE İZOLELİ) HD 626

tds

Code
NFA2X
Voltage Rating
0.6/1 kV
Standards
HD 626 S1
Conductor
Stranded Aluminium Conductor
Insulation:
XLPE (Cross Linked Polyethylene)
Construction
1 core: Straıght (marking)
2 core: Straıght (marking) – 1 Notch or number
3 core: Straıght (marking) – 1 Notch or number – 2 Notch or number
4 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or number
6 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght – EP2 1 Notch
6 core:1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or marking – EP1 Straıght – EP2 1 Notch
Technical Data
Max. Operating Temperature : 90°C
Short  Circuit  Temperature : 250°C (max.5 sec)
Operating Temperature :  -40°C to +80°C
Bending Radius : 12xD
Test Voltage : 4.0 kV
Application:
Aerial Bundle Cable (ABC) low voltage cable for overhead power distribution offering higher level of safety and
reliability and lower power losses than bare conductors.
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
1×10 10 3,7 3,08 – – – – – – 5,7 42,8
1×16 16 4,7 1,91 – – – – – – 7,1 65,0
1×25 25 5,9 1,20 – – – – – – 8,5 98,7
1×35 35 6,9 0,868 – – – – – – 9,5 129,5
1×50 50 8,1 0,641 – – – – – – 11,1 173,3
1×63 63 9,7 0,456 – – – – – – 12,7 230,2
1×70 70 10,0 0,443 – – – – – – 13,0 238,6
1×95 95 11,5 0,320 – – – – – – 14,9 314,3
1×120 120 12,8 0,253 – – – – – – 16,2 384,5
1×150 150 14,8 0,206 – – – – – – 18,2 478,0
1×185 185 16,6 0,164 – – – – – – 20,2 617,2
1×240 240 18,8 0,125 – – – – – – 22,8 781,2
1×300 300 21,2 0,100 – – – – – – 25,6 991,7
1×400 400 24,1 0,0778 – – – – – – 28,5 1295,8
1×500 500 27,2 0,0605 – – – – – – 32,0 1614,0
2×10 10 3,7 3,08 – – – – – – 11,4 86,6
2×16 16 4,7 1,91 – – – – – – 14,2 131,6
2×25 25 5,9 1,20 – – – – – – 16,9 199,8
2×35 35 6,9 0,868 – – – – – – 19,0 263,6
2×50 50 8,1 0,641 – – – – – – 22,2 350,7
2×70 70 10,0 0,443 – – – – – – 26,0 482,9
2×95 95 11,5 0,320 – – – – – – 29,8 636,1
2×120 120 12,8 0,253 – – – – – – 32,5 778,2
3×10 10 3,7 3,08 – – – – – – 12,3 130,4
3×16 16 4,7 1,91 – – – – – – 15,3 199,4
3×25 25 5,9 1,20 – – – – – – 18,3 301,7
3×35 35 6,9 0,868 – 20,5 396,6
3×50 50 8,1 0,641 – – – – – – 24,0 526,7
3×70 70 10,0 0,443 – – – – – – 28,0 725,3
3×95 95 11,5 0,320 – – – – – – 32,2 955,4
3×120 120 12,8 0,253 – – – – – – 35,1 1168,7
4×10 10 3,7 3,08 – – – – – – 13,8 173,9
4×16 16 4,7 1,91 – – – – – – 17,2 266,0
4×25 25 5,9 1,20 – – – – – – 20,5 402,5
4×35 35 6,9 0,868 – – – – – – 23,0 529,2
4×50 50 8,1 0,641 – – – – – – 26,8 702,7
4×70 70 10,0 0,443 – – – – – – 31,4 967,8
4×95 95 11,5 0,320 – – – – – – 36,0 1274,8
4×120 120 12,8 0,253 – – – – – – 39,3 1559,5
4×240 240 18,8 0,125 – – – – – – 55,1 3168,6
5×10 10 3,7 3,08 – – – – – – 15,4 217,5
5×16 16 4,7 1,91 – – – – – – 19,1 332,7
5×25 25 5,9 1,20 – – – – – – 22,8 503,4
5×35 35 6,9 0,868 – – – – – – 25,6 662,0
6×10 10 3,7 3,08 – – – – – – 17,1 261,2
6×16 16 4,7 1,91 – – – – – – 21,2 399,5
6×25 25 5,9 1,20 – – – – – – 25,3 604,5
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
3×16+25 16 4,7 1,91 – – – 6,3 – 1,38 18,3 300,5
3×16+54,6 16 4,7 1,91 – – – 9,5 – 0,630 20,4 415,1
3×25+16 16 5,9 1,20 – – – 4,7 – 1,91 19,6 368,4
3×25+35 25 5,9 1,20 – – – 7,4 – 0,986 21,4 433,9
3×25+54,6 25 5,9 1,20 – – – 9,5 – 0,630 22,9 517,5
3×35+16 35 6,9 0,868 – – – 4,7 – 1,91 23,0 463,4
3×35+50 35 6,9 0,868 – – – 8,7 – 0,720 24,3 571,9
3×35+54,6 35 6,9 0,868 – – – 9,5 – 0,630 24,8 612,5
3×35+70 35 6,9 0,868 – – – 10,5 – 0,500 25,6 661,6
3×50+25 50 8,1 0,641 – – – 6,3 – 1,38 25,5 628,7
3×50+35 50 8,1 0,641 – – – 7,4 – 0,986 26,2 659,1
3×50+54,6 50 8,1 0,641 – – – 9,5 – 0,630 27,7 742,6
3×50+70 50 8,1 0,641 – – – 10,5 – 0,500 28,5 791,8
3×70+35 70 10,0 0,443 – – – 7,4 – 0,986 29,6 857,9
3×70+50 70 10,0 0,443 – – – 8,7 – 0,720 30,6 905,8
3×70+54,6 70 10,0 0,443 – – – 9,5 – 0,630 31,1 941,4
3×70+70 70 10,0 0,443 – – – 10,5 – 0,500 32,0 990,6
3×70+95 70 10,0 0,443 – – – 12,4 – 0,343 33,1 1066,4
3×95+50 95 11,5 0,320 – – – 8,7 – 0,720 34,1 1131,8
3×95+54,6 95 11,5 0,320 – – – 9,5 – 0,630 34,6 1171,7
3×95+70 95 11,5 0,320 – – – 10,5 – 0,500 35,4 1220,8
3×95+95 95 11,5 0,320 – – – 12,4 – 0,343 36,6 1296,6
3×120+70 120 12,8 0,253 – – – 10,5 – 0,500 37,9 1435,4
3×120+95 120 12,8 0,253 – – – 12,4 – 0,343 39,0 1510,2
3×150+70 150 14,8 0,206 – – – 10,5 – 0,500 41,5 1718,8
3×150+95 150 14,8 0,206 – – – 12,4 – 0,343 42,6 1797,6
3×240+120 240 18,8 0,125 – – – 12,8 – 0,253 51,1 2766,3
4×25+16 25 5,9 1,20 – – – 4,7 – 1,91 22,1 469,3
4×25+35 25 5,9 1,20 – – – 6,9 – 0,868 23,7 534,9
4×35+16 35 6,9 0,868 – – – 4,7 – 1,91 24,3 596,1
4×35+25 35 6,9 0,868 – – – 5,9 – 1,20 25,1 630,3
4×50+25 50 8,1 0,641 – – – 5,9 – 1,20 28,8 804,8
4×95+25 95 11,5 0,320 – – – 5,9 – 1,20 37,0 1377,9
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
3×25+54,6+1×16 25 5,9 1,20 – 16 1,91 9,5 – 0,630 24,3 584,4
3×35+50+1×16 35 6,9 0,868 – 16 1,91 8,7 – 0,720 25,5 643,3
3×35+54,6+1×16 35 6,9 0,868 – 16 1,91 9,5 – 0,630 25,9 679,5
3×35+54,6+1×25 35 6,9 0,868 – 25 1,20 9,5 – 0,630 26,7 713,7
3×50+25+1×16 50 8,1 0,641 – 16 1,91 6,3 – 1,38 26,6 695,2
3×50+35+1×25 50 8,1 0,641 – 25 1,20 7,4 – 0,986 27,9 760,3
3×50+54,6+1×16 50 8,1 0,641 – 16 1,91 9,5 – 0,630 28,5 809,8
3×50+70+1×25 50 8,1 0,641 – 25 1,20 10,5 – 0,500 30,0 893,4
3×70+35+1×16 70 10,0 0,443 – 16 1,91 7,4 – 0,986 30,3 925,2
3×70+50+35 70 10,0 0,443 – 35 0,868 8,7 – 0,720 32,5 1038,0
3×70+54,6+1×16 70 10,0 0,443 – 16 1,91 9,5 – 0,630 31,6 1008,7
3×70+95+1×25 70 10,0 0,443 – 25 1,20 12,4 – 0,343 34,1 1168,9
3×95+50+1×16 95 11,5 0,320 – 16 1,91 8,7 – 0,720 34,3 1203,8
3×95+54,6+1×16 95 11,5 0,320 – 16 1,91 9,5 – 0,630 34,7 1239,4
3×95+70+50 95 11,5 0,320 – 50 0,641 10,5 – 0,500 37,5 1396,7
3×120+70+1×16 120 12,8 0,253 – 16 1,91 10,5 – 0,500 37,9 1501,9
3×120+95+70 120 12,8 0,253 – 70 0,443 12,4 – 0,343 41,8 1751,8
3×25+54,6+2×16 25 5,9 1,20 – 16 1,91 9,5 – 0,630 25,9 651,3
3×25+54,6+2×25 25 5,9 1,20 – 25 1,20 9,5 – 0,630 27,3 719,5
3×35+54,6+2×16 35 6,9 0,868 – 16 1,91 9,5 – 0,630 27,5 746,8
3×35+54,6+2×25 35 6,9 0,868 – 25 1,20 9,5 – 0,630 28,8 815,0
3×35+70+2×16 35 6,9 0,868 – 16 1,91 10,5 – 0,500 28,2 795,4
3×50+54,6+2×16 50 8,1 0,641 – 16 1,91 9,5 – 0,630 29,9 877,2
3×50+54,6+2×25 50 8,1 0,641 – 25 1,20 9,5 – 0,630 31,2 945,4
3×70+54,6+2×16 70 10,0 0,443 – 16 1,91 9,5 – 0,630 32,7 1076,5
3×70+54,6+2×25 70 10,0 0,443 – 25 1,20 9,5 – 0,630 34,0 1144,7
3×70+70+2×16 70 10,0 0,443 – 16 1,91 10,5 – 0,500 33,4 1125,7
3×70+70+2×25 70 10,0 0,443 – 25 1,20 10,5 – 0,500 34,8 1194,6
3×95+50+2×25 95 11,5 0,320 – 25 1,20 8,7 – 0,720 36,5 1339,7
3×95+54,6+2×16 95 11,5 0,320 – 16 1,91 9,5 – 0,630 35,5 1307,2
3×95+54,6+2×25 95 11,5 0,320 – 25 1,20 9,5 – 0,630 36,9 1375,4
3×120+95+2×25 120 12,8 0,253 – 25 1,20 12,4 – 0,343 40,5 1714,5
3×150+95+2×25 150 14,8 0,206 – 25 1,20 12,4 – 0,343 43,5 1999,7
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
4×25+2×16 25 5,9 1,20 – 16 1,91 – – – 23,9 536
4×25+2×25 25 5,9 1,20 – 25 1,20 – – – 25,3 604,5
4×35+2×16 35 6,9 0,868 – 16 1,91 – – – 26,0 662,8
4×35+2×25 35 6,9 0,868 – 25 1,20 – – – 27,4 730,9
4×50+2×16 50 8,1 0,641 – 16 1,91 – – – 29,2 837,2
4×50+2×25 50 8,1 0,641 – 25 1,20 – – – 30,5 905,4
4×70+2×16 70 10,0 0,443 – 16 1,91 – – – 32,9 1102,8
4×70+2×25 70 10,0 0,443 – 25 1,20 – – – 34,3 1171
4×95+2×16 95 11,5 0,320 – 16 1,91 – – – 36,7 1410,5
4×95+2×25 95 11,5 0,320 – 25 1,20 – – – 38,1 1478,7
Note1:
The vein colors mentioned above may vary according to customer demand.
Note2:
Current carrying capacities are valid at 30°C ambient temperature.