ABC (PE İZOLELİ) HD 626

ABC (PE İZOLELİ) HD 626

Category:

tds

Code
ABC
Voltage Rating
0.6/1 kV
Standards
HD 626 S1
Conductor
Stranded Aluminium Conductor
Insulation:
PE (Polyethylene)
Construction
1 core: Straıght (marking)
2 core: Straıght (marking) – 1 Notch or number
3 core: Straıght (marking) – 1 Notch or number – 2 Notch or number
4 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght
5 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or number
6 core: Straıght (marking) – 1 Notch or number – 2 Notch or number – 3 Notch or number – EP1 Straıght – EP2 1 Notch
6 core:1 Notch or number – 2 Notch or number – 3 Notch or number – 4 Notch or marking – EP1 Straıght – EP2 1 Notch
Technical Data
Max. Operating Temperature : 90°C
Short  Circuit  Temperature : 250°C (max.5 sec)
Operating Temperature :  -40°C to +80°C
Bending Radius : 12xD
Test Voltage : 4.0 kV
Application:
Aerial Bundle Cable (ABC) low voltage cable for overhead power distribution offering higher level of safety and
reliability and lower power losses than bare conductors.
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
1×10 10 3,7 3,08 – – – – – – 5,7 47,0
1×16 16 4,7 1,91 – – – – – – 7,1 66,0
1×25 25 5,9 1,20 – – – – – – 8,7 101,2
1×35 35 6,9 0,868 – – – – – – 10,1 137,0
1×50 50 8,1 0,641 – – – – – – 11,3 176,0
1×63 63 9,7 0,456 – – – – – – 13,3 242,2
1×70 70 10,0 0,443 – – – – – – 13,6 245,6
1×95 95 11,5 0,320 – – – – – – 15,1 318,0
1×120 120 12,8 0,253 – – – – – – 16,4 388,5
1×150 150 14,8 0,206 – – – – – – 18,4 480,6
2×10 10 3,7 3,08 – – – – – – 11,4 95,1
2×16 16 4,7 1,91 – – – – – – 14,2 133,6
2×25 25 5,9 1,20 – – – – – – 17,3 204,8
2×35 35 6,9 0,868 – – – – – – 20,2 277,2
2×50 50 8,1 0,641 – – – – – – 22,6 356,3
2×70 70 10,0 0,443 – – – – – – 27,2 497,0
2×95 95 11,5 0,320 – – – – – – 30,2 643,7
2×120 120 12,8 0,253 – – – – – – 32,9 786,4
3×25 25 5,9 1,20 – – – – – – 18,7 307,6
3×50 50 8,1 0,641 – – – – – – 24,4 534,9
4×10 10 3,7 3,08 – – – – – – 13,8 189,5
4×16 16 4,7 1,91 – – – – – – 17,2 267,6
4×25 25 5,9 1,20 – – – – – – 21,0 410,5
4×35 35 6,9 0,868 – – – – – – 24,4 555,6
4×50 50 8,1 0,641 – – – – – – 27,3 714,0
4×70 70 10,0 0,443 – – – – – – 32,9 996,2
4×95 95 11,5 0,320 – – – – – – 36,5 1289,7
4×120 120 12,8 0,253 – – – – – – 39,8 1575,7
5×16 16 4,7 1,91 – – – – – – 19,1 335,2
5×25 25 5,9 1,20 – – – – – – 23,4 513,4
5×35 35 6,9 0,868 – – – – – – 27,2 695,4
6×16 16 4,7 1,91 – – – – – – 21,2 402,5
6×25 25 5,9 1,20 – – – – – – 25,9 617,1
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
3×16+16 16 4,7 1,91 – – – 4,7 – 1,91 17,2 267,6
3×16+25 16 4,7 1,91 – – – 6,3 – 1,38 18,4 303,5
3×25+25 25 5,9 1,20 – – – 6,3 – 1,38 21,2 410,5
3×25+35 25 5,9 1,20 – – – 7,4 – 0,986 22,1 446,7
3×25+54,6 25 5,9 1,20 – – – 9,5 – 0,630 23,4 526,9
3×35+35 35 6,9 0,868 – – – 7,4 – 0,986 24,7 557,1
3×35+50 35 6,9 0,868 – – – 8,7 – 0,720 25,5 595,2
3×35+54,6 35 6,9 0,868 – – – 9,5 – 0,630 26,0 635,8
3×50+35 50 8,1 0,641 – – – 7,4 – 0,986 26,9 674,4
3×50+50 50 8,1 0,641 – – – 8,7 – 0,720 27,7 715,7
3×50+54,6 50 8,1 0,641 – – – 9,5 – 0,630 28,1 754,6
3×50+70 50 8,1 0,641 – – – 10,5 – 0,500 29,0 799,6
3×70+50 70 10,0 0,443 – – – 8,7 – 0,720 31,9 925,7
3×70+54,6 70 10,0 0,443 – – – 9,5 – 0,630 32,3 966,3
3×70+70 70 10,0 0,443 – – – 10,5 – 0,500 33,1 1013,5
3×70+95 70 10,0 0,443 – – – 12,4 – 0,343 34,3 1072,6
3×95+54,6 95 11,5 0,320 – – – 9,5 – 0,630 35,0 1186,4
3×95+70 95 11,5 0,320 – – – 10,5 – 0,500 35,9 1231,4
3×95+95 95 11,5 0,320 – – – 12,4 – 0,343 37,0 1308,1
3×120+70 120 12,8 0,253 – – – 10,5 – 0,500 38,3 1449,7
3×120+95 120 12,8 0,253 – – – 12,4 – 0,343 39,5 1520,0
3×150+70 150 14,8 0,206 – – – 10,5 – 0,500 41,9 1736,1
3×150+95 150 14,8 0,206 – – – 12,4 – 0,343 43,1 1803,2
4×25+35 25 5,9 1,20 – – – 6,9 – 0,868 24,4 549,8
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
3×25+54,6+1×16 25 5,9 1,20 – 16 1,91 9,5 – 0,630 24,7 594,3
3×35+50+1×16 35 6,9 0,868 – 16 1,91 8,7 – 0,720 26,6 667,7
3×35+54,6+1×16 35 6,9 0,868 – 16 1,91 9,5 – 0,630 27,0 703,5
3×35+54,6+1×25 35 6,9 0,868 – 25 1,20 9,5 – 0,630 27,9 739,2
3×50+54,6+1×16 50 8,1 0,641 – 16 1,91 9,5 – 0,630 29,0 822,0
3×50+70+1×25 50 8,1 0,641 – 25 1,20 10,5 – 0,500 30,5 902,9
3×70+54,6+1×16 70 10,0 0,443 – 16 1,91 9,5 – 0,630 32,7 1034,1
3×70+95+1×25 70 10,0 0,443 – 25 1,20 12,4 – 0,343 35,3 1189,3
3×95+54,6+1×16 95 11,5 0,320 – 16 1,91 9,5 – 0,630 35,1 1254,6
3×95+70+1×16 95 11,5 0,320 – 16 1,91 10,5 – 0,500 35,8 1299,7
3×120+70+1×16 120 12,8 0,253 – 16 1,91 10,5 – 0,500 38,0 1514,2
3×25+54,6+2×16 25 5,9 1,20 – 16 1,91 9,5 – 0,630 26,3 662,1
3×25+54,6+2×25 25 5,9 1,20 – 25 1,20 9,5 – 0,630 27,9 733,5
3×35+54,6+2×16 35 6,9 0,868 – 16 1,91 9,5 – 0,630 28,5 771,3
3×35+54,6+2×25 35 6,9 0,868 – 25 1,20 9,5 – 0,630 30,0 842,7
3×50+54,6+2×16 50 8,1 0,641 – 16 1,91 9,5 – 0,630 30,3 890,1
3×50+54,6+2×25 50 8,1 0,641 – 25 1,20 9,5 – 0,630 31,8 961,5
3×70+54,6+2×16 70 10,0 0,443 – 16 1,91 9,5 – 0,630 33,7 1102,2
3×70+54,6+2×25 70 10,0 0,443 – 25 1,20 9,5 – 0,630 35,2 1173,6
3×95+50+2×25 95 11,5 0,320 – 25 1,20 8,7 – 0,720 37,2 1358,0
3×95+54,6+2×16 95 11,5 0,320 – 16 1,91 9,5 – 0,630 35,9 1323,0
3×95+54,6+2×25 95 11,5 0,320 – 25 1,20 9,5 – 0,630 37,5 1394,4
3×120+95+2×25 120 12,8 0,253 – 25 1,20 12,4 – 0,343 41,1 1728,7
3×150+95+2×25 150 14,8 0,206 – 25 1,20 12,4 – 0,343 44,1 2009,3
INSULATED WIRES MESSENGER FINISHED CABLE
Phase Conductor Main Distrubition Line
Nominal Cross Section Cross Section Dia.of Conductor Resistance at 20°C Current Carrying Capacity Cross Section Resistance
at 20°C
Dia.of Conductor Min.Tensile
Strenght
Resistance
at 20°C
Diameter Of Cable Net Weight
mm² mm² mm ohm/km A mm² ohm/km mm kN ohm/km mm kg/km
4×25+2×16 25 5,9 1,20 – 16 1,91 – – – 24,3 545,4
4×25+2×25 25 5,9 1,20 – 25 1,20 – – – 25,9 617,1
4×35+2×16 35 6,9 0,868 – 16 1,91 – – – 27,2 690,4
4×35+2×25 35 6,9 0,868 – 25 1,20 – – – 28,7 761,9
4×50+2×16 50 8,1 0,641 – 16 1,91 – – – 29,6 849,4
4×50+2×25 50 8,1 0,641 – 25 1,20 – – – 31,1 920,8
4×70+2×16 70 10,0 0,443 – 16 1,91 – – – 34,1 1132,2
4×70+2×25 70 10,0 0,443 – 25 1,20 – – – 35,7 1203,6
4×95+2×16 95 11,5 0,320 – 16 1,91 – – – 37,1 1426,6
4×95+2×25 95 11,5 0,320 – 25 1,20 – – – 38,7 1498
Note1:
The vein colors mentioned above may vary according to customer demand.
Note2:
Current carrying capacities are valid at 30°C ambient temperature.